Line 4: Line 4:
  
 Some details on [[ge:diesel generators]], terminology, factors to consider, and recommended features.  Some details on [[ge:diesel generators]], terminology, factors to consider, and recommended features. 
 +  * [[ge:diesel-generators|Diesel Generators]]
 +  * [[ge:prime-vs-standby|Prime Power vs Standby Power Ratings]]
 +  * [[ge:heaters|Generator Heater Design]]
 +  * [[ge:standby-failure|Generator Standby ]]
  
 The diesel generator sets for this sample project are sized for 30kw continuous/baseload, or 38kw [[ge:prime-vs-standby|prime power]]. The [[cp:start|Control System]] will automatically start a second generator if the first generator reaches 80% of its capacity, synchronize and operate them in parallel. When the load drops below 70% of the single genset capacity it will automatically unload and cool down the second genset. If the running generator shuts down due to a fault the second generator will automatically start and carry the load; if possible (in the case of a critical warning, like high water temperature or low coolant) the load will be transferred automatically before shut down.  The diesel generator sets for this sample project are sized for 30kw continuous/baseload, or 38kw [[ge:prime-vs-standby|prime power]]. The [[cp:start|Control System]] will automatically start a second generator if the first generator reaches 80% of its capacity, synchronize and operate them in parallel. When the load drops below 70% of the single genset capacity it will automatically unload and cool down the second genset. If the running generator shuts down due to a fault the second generator will automatically start and carry the load; if possible (in the case of a critical warning, like high water temperature or low coolant) the load will be transferred automatically before shut down. 
Line 22: Line 26:
       * {{:datasheets:jd_4045df150_d.pdf|}}       * {{:datasheets:jd_4045df150_d.pdf|}}
       * Subtract 20% from the 60Hz rating for 50Hz       * Subtract 20% from the 60Hz rating for 50Hz
-    * Speed control - [[http://governors-america.com/Governors America]] {{:datasheets:gac_controller_esd5500cond.pdf|ESD5500E}} [[http://governors-america.com/esd5500e_series.html|controller]] with {{:datasheets:gac_actuator_100_series_-_pti2040.pdf|ADC-100-12}} [[http://governors-america.com/1oo_series_-_stanadyne_d_series_fuel_injection_pumps.html|actuator]]+    * Speed control - [[http://governors-america.com |Governors America]] {{:datasheets:gac_controller_esd5500cond.pdf|ESD5500E}} [[https://www.governors-america.com/categories/esd5500e-series|controller]] with {{:datasheets:gac_actuator_100_series_-_pti2040.pdf|ADC-100-12}} [[https://www.governors-america.com/products/adc100-12|actuator]]
   * **Engine Sensors**   * **Engine Sensors**
     * Water Temperature Sender (provides temperature indication & warning)     * Water Temperature Sender (provides temperature indication & warning)
Line 42: Line 46:
     * Model [[http://www.marathonelectric.com/MGPS/details.jsp?item=363PSL3127&voltage=220Y&hertz=50&phase=3|363PSL3127]] [[http://www.marathonelectric.com/generators/docs/perf/363PSL3127T50.pdf|Performance Data]]     * Model [[http://www.marathonelectric.com/MGPS/details.jsp?item=363PSL3127&voltage=220Y&hertz=50&phase=3|363PSL3127]] [[http://www.marathonelectric.com/generators/docs/perf/363PSL3127T50.pdf|Performance Data]]
     * Compare with dedicated single-phase model [[http://www.marathonelectric.com/MGPS/details.jsp?item=431PSL6224&voltage=220/110//110&hertz=50&phase=Dedicated%201|431PSL6224]] [[http://www.marathonelectric.com/generators/docs/perf/431PSL6224S50.pdf|Performance Data]]     * Compare with dedicated single-phase model [[http://www.marathonelectric.com/MGPS/details.jsp?item=431PSL6224&voltage=220/110//110&hertz=50&phase=Dedicated%201|431PSL6224]] [[http://www.marathonelectric.com/generators/docs/perf/431PSL6224S50.pdf|Performance Data]]
 +    * Note: generator windings in high humidity or tropical environments can experience insulation failure in just two or three years due to absorption of moisture in the windings. The Mariner model somewhat helps to prevent this; for the best protection, see the article on [[heaters |generator heaters]]. 
  
  
 The gensets can be built to order by [[:Martin Machinery]]. Contact them for a quote and if you want to make changes from the standard design (generator size, engine size, model, features, etc.).  The gensets can be built to order by [[:Martin Machinery]]. Contact them for a quote and if you want to make changes from the standard design (generator size, engine size, model, features, etc.). 