Site Tools


reference:awg-iec-wire

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
Next revision
Previous revision
reference:awg-iec-wire [2017/11/07 23:00] – link to hmwire.com Alan Sheareference:awg-iec-wire [2023/11/10 00:49] (current) Alan Shea
Line 2: Line 2:
 ======AWG-IEC Wire Gauges==== ======AWG-IEC Wire Gauges====
  
-American Wire Gauge (AWG) and IEC (mm<sup>2</sup>) wire sizes are often hard to correlate. There are many references on the internet, but none that gave enough information to make a useful comparison+American Wire Gauge (AWG) and IEC (mm<sup>2</sup>) wire sizes. 
  
 <WRAP group> <WRAP group>
 <WRAP column 400px> <WRAP column 400px>
-^  AWG/\\ kcmil  ^  Area Circular Mils  ^  Amperes  ^^^  mm2  + 
- :::  ^ :::  ^  TW/UF (60C)  ^  THHW (75C)  ^  THHN (90C)  ^ ::: ^ +^  AWG/\\ kcmil  ^  Area Circular Mils  ^  Amperes                                  ||^  mm2    
-|  18  |  1620  |  --  |  --  |  --  |   0.8   |  +^ :::            ^ :::                  ^  TW/UF (60C)  ^  THHW (75C)  ^  THHN (90C)  ^ :::     
-|  16  |  2580  |  --  |  --  |  --  |   1.3   |  +|  18            |  1620                |  --           |  --          |  --           0.8    
-|  14*  |  4110  |  20 (15)  |  20 (15)  |  25 (20)  |   2.1   |  +|  16            |  2580                |  --           |  --          |  --           1.3    
-|  12*  |  6530  |  25 (20)  |  25 (20)  |  30 (20)  |   3.3   |  +|  14*           |  4110                |  20 (15)      |  20 (15)     |  25 (20)     |  2.1    
-|  10*  |  10,380  |  30  |  35 (30)  |  40 (30)  |   5.3   |  +|  12*           |  6530                |  25 (20)      |  25 (20)     |  30 (20)     |  3.3    
-|  8  |  16,510  |  40  |  50  |  55  |   8.4   |  +|  10*           |  10,380              |  30           |  35 (30)     |  40 (30)     |  5.3    
-|  6  |  26,240  |  55  |  65  |  75  |   13.3   |  +|  8             |  16,510              |  40           |  50          |  55           8.4    
-|  4  |  41,740  |  70  |  85  |  95  |   21.1   |  +|  6             |  26,240              |  55           |  65          |  75           13.3   | 
-|  3  |  52,620  |  85  |  100  |  110  |   26.7   |  +|  4             |  41,740              |  70           |  85          |  95           21.1   | 
-|  2  |  66,360  |  95  |  115  |  130  |   33.6   |  +|  3             |  52,620              |  85           |  100         |  110         |  26.7   | 
-|  1  |  83,690  |  110  |  130  |  150  |   42.4   |  +|  2             |  66,360              |  95           |  115         |  130         |  33.6   | 
-|  1/0  |  105,600  |  125  |  150  |  170  |   53.5   |  +|  1             |  83,690              |  110          |  130         |  150         |  42.4   | 
-|  2/0  |  133,100  |  145  |  175  |  195  |   67.4   |  +|  1/0           |  105,600             |  125          |  150         |  170         |  53.5   | 
-|  3/0  |  167,800  |  165  |  200  |  225  |   85.0   |  +|  2/0           |  133,100             |  145          |  175         |  195         |  67.4   | 
-|  4/0  |  211,600  |  195  |  230  |  260  |   107.2   |  +|  3/0           |  167,800             |  165          |  200         |  225         |  85.0   | 
-|  250  |  250,000  |  215  |  255  |  290  |   126.7   |  +|  4/0           |  211,600             |  195          |  230         |  260         |  107.2  
-|  300  |  300,000  |  240  |  285  |  320  |   152.0   |  +|  250           |  250,000             |  215          |  255         |  290         |  126.7  
-|  350  |  350,000  |  260  |  310  |  350  |   177.3   |  +|  300           |  300,000             |  240          |  285         |  320         |  152.0  
-|  400  |  400,000  |  280  |  335  |  380  |   202.7   |  +|  350           |  350,000             |  260          |  310         |  350         |  177.3  
-|  500  |  500,000  |  320  |  380  |  430  |   253.4   |  +|  400           |  400,000             |  280          |  335         |  380         |  202.7  
-|  600  |  600,000  |  355  |  420  |  475  |   304.0   |  +|  500           |  500,000             |  320          |  380         |  430         |  253.4  
-|  700  |  700,000  |  385  |  460  |  520  |   354.7   |  +|  600           |  600,000             |  355          |  420         |  475         |  304.0  
-|  750  |  750,000  |  400  |  475  |  535  |   380.0   |  +|  700           |  700,000             |  385          |  460         |  520         |  354.7  
-|  800  |  800,000  |  410  |  490  |  555  |   405.4   |  +|  750           |  750,000             |  400          |  475         |  535         |  380.0  
-|  900  |  900,000  |  435  |  520  |  585  |   456.0   |  +|  800           |  800,000             |  410          |  490         |  555         |  405.4  
-|  1000  |  1000,000  |  455  |  545  |  615  |   506.7   +|  900           |  900,000             |  435          |  520         |  585         |  456.0  
 +|  1000          |  1000,000            |  455          |  545         |  615         |  506.7  |
  
 * Maximum overcurrent protection: \\ #14 = 15A, #12 = 20A, #10 = 30A * Maximum overcurrent protection: \\ #14 = 15A, #12 = 20A, #10 = 30A
Line 41: Line 42:
  
 <WRAP column 270px> <WRAP column 270px>
-^  IEC mm2  ^  Circular Mils  ^  Amperes  ^^ +^  IEC mm2  ^  Circular Mils  ^  Amperes                                || 
-^  :::  :::  ^  Free Air, 70C PVC  ^  In Wall, 70C PVC  ^ +:::       | :::             ^  Free Air, 70C PVC  ^  In Wall, 70C PVC  ^ 
-|  0.5  |  987     --  |    --  |  +|  0.5      |  987             --                 |  --                
-|  0.75  |  1481  |  --  |  --  |  +|  0.75     |  1481           |  --                 |  --                
-|  1.5  |  2961    17.5   |  13  |  +|  1.5      |  2961            17.5               |  13                
-|  2.5  |  4935  |  24  |  17.5  |  +|  2.5      |  4935           |  24                 |  17.5              
-|  4  |  7896  |  32  |  23  |  +|  4        |  7896           |  32                 |  23                
-|  6  |  11,844  |  41  |  29  |  +|  6        |  11,844         |  41                 |  29                
-|  10  |  19,740  |  57  |  39  |  +|  10       |  19,740         |  57                 |  39                
-|  16  |  31,584  |  76  |  52  |  +|  16       |  31,584         |  76                 |  52                
-|  25  |  49,350  |  96  |  68  |  +|  25       |  49,350         |  96                 |  68                
-|  35  |  69,090  |  119  |  83  |  +|  35       |  69,090         |  119                |  83                
-|  50  |  98,700  |  144  |  99  |  +|  50       |  98,700         |  144                |  99                
-|  70  |  13,8180  |  184  |  125  |  +|  70       |  13,8180        |  184                |  125               
-|  95  |  187,530  |  223  |  150  |  +|  95       |  187,530        |  223                |  150               
-|  120  |  236,880  |  259  |  172  |  +|  120      |  236,880        |  259                |  172               
-|  150  |  296,100  |  299  |  196  |  +|  150      |  296,100        |  299                |  196               
-|  185  |  365,190  |  341  |  223  |  +|  185      |  365,190        |  341                |  223               
-|  240  |  473,760  |  403  |  261  |  +|  240      |  473,760        |  403                |  261               
-|  300  |  592,200  |  464  |  298  +|  300      |  592,200        |  464                |  298               |
  
   * //IEC 60364-5-52, Table A.52.4//   * //IEC 60364-5-52, Table A.52.4//
Line 84: Line 85:
 <WRAP column 290px> <WRAP column 290px>
  
-{{ :reference:awg-iec_wires.png?280| }}+{{ :reference:awg-iec_wires.png?direct&280| }}
 </WRAP> </WRAP>
 </WRAP> </WRAP>
Line 91: Line 92:
 [[wp>American_wire_gauge#Tables_of_AWG_wire_sizes |AWG wire sizes]] [[wp>American_wire_gauge#Tables_of_AWG_wire_sizes |AWG wire sizes]]
  
-[[http://www.hmwire.com/wirediminsions.html |AWG mathematical relationships of sizes explained]]+[[https://web.archive.org/web/20180314050616/http://www.hmwire.com/wirediminsions.html|AWG mathematical relationships of sizes explained]] -- //"Every 3 gauge sizes the resistance, mass per unit, and cross section will double or halve."//
  
  
 ---- ----
- +===Downloads==
-\\ +
 {{filelist>:reference:awg*&style=table&tableheader=1&tableshowdate=1&tableshowsize=1}} {{filelist>:reference:awg*&style=table&tableheader=1&tableshowdate=1&tableshowsize=1}}
  
 +<wrap hide>[[http://wiresizecalculator.net/tables/groundconductortable.htm|ground conductor]]</wrap>
reference/awg-iec-wire.1510095611.txt.gz · Last modified: 2018/05/28 22:28 (external edit)