 ======AWG-IEC Wire Gauges==== ======AWG-IEC Wire Gauges====
  
-American Wire Gauge (AWG) and IEC wire sizes are often hard to correlate. There are many references on the internet, but none that gave enough information to really compare. So I wrote my own reference to compare the area of each size more usefully+American Wire Gauge (AWG) and IEC (mm<sup>2</sup>wire sizes. 
  
-<box 720px> +<WRAP group
-{{ :reference:awg-iec_wires.png?720| }} +<WRAP column 400px>
-</box>+
  
 +^  AWG/\\ kcmil  ^  Area Circular Mils  ^  Amperes                                  ||^  mm2    ^
 +^ :::            ^ :::                  ^  TW/UF (60C)  ^  THHW (75C)  ^  THHN (90C)  ^ :::     ^
 +|  18            |  1620                |  --            --          |  --          |  0.8    |
 +|  16            |  2580                |  --            --          |  --          |  1.3    |
 +|  14*            4110                |  20 (15)      |  20 (15)      25 (20)      2.1    |
 +|  12*            6530                |  25 (20)      |  25 (20)      30 (20)      3.3    |
 +|  10*            10,380              |  30            35 (30)      40 (30)      5.3    |
 +|  8              16,510              |  40            50          |  55          |  8.4    |
 +|  6              26,240              |  55            65          |  75          |  13.3   |
 +|  4              41,740              |  70            85          |  95          |  21.1   |
 +|  3              52,620              |  85            100          110          26.7   |
 +|  2              66,360              |  95            115          130          33.6   |
 +|  1              83,690              |  110          |  130          150          42.4   |
 +|  1/0            105,600              125          |  150          170          53.5   |
 +|  2/0            133,100              145          |  175          195          67.4   |
 +|  3/0            167,800              165          |  200          225          85.0   |
 +|  4/0            211,600              195          |  230          260          107.2  |
 +|  250            250,000              215          |  255          290          126.7  |
 +|  300            300,000              240          |  285          320          152.0  |
 +|  350            350,000              260          |  310          350          177.3  |
 +|  400            400,000              280          |  335          380          202.7  |
 +|  500            500,000              320          |  380          430          253.4  |
 +|  600            600,000              355          |  420          475          304.0  |
 +|  700            700,000              385          |  460          520          354.7  |
 +|  750            750,000              400          |  475          535          380.0  |
 +|  800            800,000              410          |  490          555          405.4  |
 +|  900            900,000              435          |  520          585          456.0  |
 +|  1000          |  1000,000            |  455          |  545          615          506.7  |
 +
 +* Maximum overcurrent protection: \\ #14 = 15A, #12 = 20A, #10 = 30A
 +
 +//NEC 2007, Chap 9, Table 8, \\ via Ugly's Electrical Ref 2008, pp71, 73//
 +</WRAP>
 +
 +<WRAP column 270px>
 +^  IEC mm2  ^  Circular Mils  ^  Amperes                                ||
 +| :::       | :::              Free Air, 70C PVC  ^  In Wall, 70C PVC  ^
 +|  0.5      |  987            |  --                  --                |
 +|  0.75      1481            --                  --                |
 +|  1.5      |  2961            17.5                13                |
 +|  2.5      |  4935            24                  17.5              |
 +|  4        |  7896            32                  23                |
 +|  6        |  11,844          41                  29                |
 +|  10        19,740          57                  39                |
 +|  16        31,584          76                  52                |
 +|  25        49,350          96                  68                |
 +|  35        69,090          119                |  83                |
 +|  50        98,700          144                |  99                |
 +|  70        13,8180        |  184                |  125               |
 +|  95        187,530        |  223                |  150               |
 +|  120      |  236,880        |  259                |  172               |
 +|  150      |  296,100        |  299                |  196               |
 +|  185      |  365,190        |  341                |  223               |
 +|  240      |  473,760        |  403                |  261               |
 +|  300      |  592,200        |  464                |  298               |
 +
 +  * //IEC 60364-5-52, Table A.52.4//
 +  * Fig. G20, http://tinyurl.com/2u3pzqd
 +</WRAP>
 <WRAP clear></WRAP> <WRAP clear></WRAP>
 +<WRAP column 450px>
  
 +===Short-time Withstand Rating===
 +Copper conductors and bolted connections withstand rating:
 +  * 1 Ampere for 5 seconds per: 
 +    * 30 circular mils (bare wire)
 +    * 42.25 circular mils (75°C insulated wire)
 +//NEC 250-94, 250-95//
  
 +===Conversions===
 +  * kcmil = Square Inches x 1273
 +  * kcmil = Square Millimeters x 1.974
 +  * mm2 = kcmil x 0.5067
 +
 +//2007 Erico Cadweld Catalog, Technical Information (page B-4)//
 +</WRAP>
 +<WRAP column 290px>
 +
 +{{ :reference:awg-iec_wires.png?direct&280| }}
 +</WRAP>
 +</WRAP>
 +<WRAP clear></WRAP>
 +\\ \\ 
 +[[wp>American_wire_gauge#Tables_of_AWG_wire_sizes |AWG wire sizes]]
 +
 +[[https://web.archive.org/web/20180314050616/http://www.hmwire.com/wirediminsions.html|AWG mathematical relationships of sizes explained]] -- //"Every 3 gauge sizes the resistance, mass per unit, and cross section will double or halve."//
 +
 +
 +----
 +===Downloads==
 {{filelist>:reference:awg*&style=table&tableheader=1&tableshowdate=1&tableshowsize=1}} {{filelist>:reference:awg*&style=table&tableheader=1&tableshowdate=1&tableshowsize=1}}
 +
 +<wrap hide>[[http://wiresizecalculator.net/tables/groundconductortable.htm|ground conductor]]</wrap>
reference/awg-iec-wire.1433415616.txt.gz · Last modified: 2018/05/28 22:28 (external edit)