 ======AWG-IEC Wire Gauges==== ======AWG-IEC Wire Gauges====
  
-American Wire Gauge (AWG) and IEC (mm<sup>2</sup>) wire sizes are often hard to correlate. There are many references on the internet, but none that gave enough information to make a useful comparison+American Wire Gauge (AWG) and IEC (mm<sup>2</sup>) wire sizes. 
  
 <WRAP group> <WRAP group>
 <WRAP column 400px> <WRAP column 400px>
-^  AWG/\\ kcmil  ^  Area \\ Circ Mils  ^  TW/UF (60C)  ^  THHW (75C)  ^  THHN (90C)  ^  mm2  ^ 
-|  18  |  1620  |  --  |  --  |  --  |   0.8    
-|  16  |  2580  |  --  |  --  |  --  |   1.3    
-|  14*  |  4110  |  20 (15)  |  20 (15)  |  25 (20)  |   2.1    
-|  12*  |  6530  |  25 (20)  |  25 (20)  |  30 (20)  |   3.3    
-|  10*  |  10,380  |  30  |  35 (30)  |  40 (30)  |   5.3    
-|  8  |  16,510  |  40  |  50  |  55  |   8.4    
-|  6  |  26,240  |  55  |  65  |  75  |   13.3    
-|  4  |  41,740  |  70  |  85  |  95  |   21.1    
-|  3  |  52,620  |  85  |  100  |  110  |   26.7    
-|  2  |  66,360  |  95  |  115  |  130  |   33.6    
-|  1  |  83,690  |  110  |  130  |  150  |   42.4    
-|  1/0  |  105,600  |  125  |  150  |  170  |   53.5    
-|  2/0  |  133,100  |  145  |  175  |  195  |   67.4    
-|  3/0  |  167,800  |  165  |  200  |  225  |   85.0    
-|  4/0  |  211,600  |  195  |  230  |  260  |   107.2    
-|  250  |  250,000  |  215  |  255  |  290  |   126.7    
-|  300  |  300,000  |  240  |  285  |  320  |   152.0    
-|  350  |  350,000  |  260  |  310  |  350  |   177.3    
-|  400  |  400,000  |  280  |  335  |  380  |   202.7    
-|  500  |  500,000  |  320  |  380  |  430  |   253.4    
-|  600  |  600,000  |  355  |  420  |  475  |   304.0    
-|  700  |  700,000  |  385  |  460  |  520  |   354.7    
-|  750  |  750,000  |  400  |  475  |  535  |   380.0    
-|  800  |  800,000  |  410  |  490  |  555  |   405.4    
-|  900  |  900,000  |  435  |  520  |  585  |   456.0    
-|  1000  |  1000,000  |  455  |  545  |  615  |   506.7    
  
-  * Maximum overcurrent protection for #14 = 15A, #12 = 20A, #10 = 30A +^  AWG/\\ kcmil  ^  Area Circular Mils  ^  Amperes                                  ||^  mm2    ^ 
-  //NEC 2007, Chap 9, Table 8, \\ via Ugly's Electrical Ref 2008, pp71, 73//+^ :::            ^ :::                  ^  TW/UF (60C)  ^  THHW (75C)  ^  THHN (90C)  ^ :::     ^ 
 +|  18            |  1620                |  --            --          |  --          |  0.8    | 
 +|  16            |  2580                |  --            --          |  --          |  1.3    | 
 +|  14*            4110                |  20 (15)      |  20 (15)      25 (20)      2.1    | 
 +|  12*            6530                |  25 (20)      |  25 (20)      30 (20)      3.3    | 
 +|  10*            10,380              |  30            35 (30)      40 (30)      5.3    | 
 +|  8              16,510              |  40            50          |  55          |  8.4    | 
 +|  6              26,240              |  55            65          |  75          |  13.3   
 +|  4              41,740              |  70            85          |  95          |  21.1   | 
 +|  3              52,620              |  85            100          110          26.7   | 
 +|  2              66,360              |  95            115          130          33.6   | 
 +|  1              83,690              |  110          |  130          150          42.4   | 
 +|  1/0            105,600              125          |  150          170          53.5   | 
 +|  2/0            133,100              145          |  175          195          67.4   | 
 +|  3/0            167,800              165          |  200          225          85.0   | 
 +|  4/0            211,600              195          |  230          260          107.2  | 
 +|  250            250,000              215          |  255          290          126.7  | 
 +|  300            300,000              240          |  285          320          152.0  | 
 +|  350            350,000              260          |  310          350          177.3  | 
 +|  400            400,000              280          |  335          380          202.7  | 
 +|  500            500,000              320          |  380          430          253.4  | 
 +|  600            600,000              355          |  420          475          304.0  | 
 +|  700            700,000              385          |  460          520          354.7  | 
 +|  750            750,000              400          |  475          535          380.0  | 
 +|  800            800,000              410          |  490          555          405.4  | 
 +|  900            900,000              435          |  520          585          456.0  | 
 +|  1000          |  1000,000            |  455          |  545          615          506.7  | 
 + 
 +* Maximum overcurrent protection: \\ #14 = 15A, #12 = 20A, #10 = 30A 
 + 
 +//NEC 2007, Chap 9, Table 8, \\ via Ugly's Electrical Ref 2008, pp71, 73//
 </WRAP> </WRAP>
  
-<WRAP column 250px+<WRAP column 270px
-^ IEC mm2 ^ Circ Mils ^ Free Air 70C PVC ^ in wall 70C PVC ^ + IEC mm2   Circular Mils   Amperes                                || 
-|  0.5  |  987  |    --  |    --  |  +| :::       | :::             ^  Free Air70C PVC   In Wall, 70C PVC  
-|  0.75  |  1481  |  --  |  --  |  +|  0.5      |  987             --                 |  --                
-|  1.5  |  2961    17.5   |  13  |  +|  0.75     |  1481           |  --                 |  --                
-|  2.5  |  4935  |  24  |  17.5  |  +|  1.5      |  2961            17.5               |  13                
-|  4  |  7896  |  32  |  23  |  +|  2.5      |  4935           |  24                 |  17.5              
-|  6  |  11,844  |  41  |  29  |  +|  4        |  7896           |  32                 |  23                
-|  10  |  19,740  |  57  |  39  |  +|  6        |  11,844         |  41                 |  29                
-|  16  |  31,584  |  76  |  52  |  +|  10       |  19,740         |  57                 |  39                
-|  25  |  49,350  |  96  |  68  |  +|  16       |  31,584         |  76                 |  52                
-|  35  |  69,090  |  119  |  83  |  +|  25       |  49,350         |  96                 |  68                
-|  50  |  98,700  |  144  |  99  |  +|  35       |  69,090         |  119                |  83                
-|  70  |  13,8180  |  184  |  125  |  +|  50       |  98,700         |  144                |  99                
-|  95  |  187,530  |  223  |  150  |  +|  70       |  13,8180        |  184                |  125               
-|  120  |  236,880  |  259  |  172  |  +|  95       |  187,530        |  223                |  150               
-|  150  |  296,100  |  299  |  196  |  +|  120      |  236,880        |  259                |  172               
-|  185  |  365,190  |  341  |  223  |  +|  150      |  296,100        |  299                |  196               
-|  240  |  473,760  |  403  |  261  |  +|  185      |  365,190        |  341                |  223               
-|  300  |  592,200  |  464  |  298  +|  240      |  473,760        |  403                |  261               
 +|  300      |  592,200        |  464                |  298               |
  
   * //IEC 60364-5-52, Table A.52.4//   * //IEC 60364-5-52, Table A.52.4//
   * Fig. G20, http://tinyurl.com/2u3pzqd   * Fig. G20, http://tinyurl.com/2u3pzqd
 </WRAP> </WRAP>
-<WRAP column 290px> +<WRAP clear></WRAP
-{{ :reference:awg-iec_wires.png?280| }} +<WRAP column 450px>
-</WRAP>+
  
 ===Short-time Withstand Rating=== ===Short-time Withstand Rating===
-Copper conductors and bolted connections withstand rating: (NEC 250-94, 250-95)+Copper conductors and bolted connections withstand rating:
   * 1 Ampere for 5 seconds per:    * 1 Ampere for 5 seconds per: 
     * 30 circular mils (bare wire)     * 30 circular mils (bare wire)
     * 42.25 circular mils (75°C insulated wire)     * 42.25 circular mils (75°C insulated wire)
 +//NEC 250-94, 250-95//
  
 ===Conversions=== ===Conversions===
Line 78: Line 82:
  
 //2007 Erico Cadweld Catalog, Technical Information (page B-4)// //2007 Erico Cadweld Catalog, Technical Information (page B-4)//
- 
 </WRAP> </WRAP>
 +<WRAP column 290px>
  
 +{{ :reference:awg-iec_wires.png?direct&280| }}
 +</WRAP>
 +</WRAP>
 <WRAP clear></WRAP> <WRAP clear></WRAP>
 +\\ \\ 
 +[[wp>American_wire_gauge#Tables_of_AWG_wire_sizes |AWG wire sizes]]
  
 +[[https://web.archive.org/web/20180314050616/http://www.hmwire.com/wirediminsions.html|AWG mathematical relationships of sizes explained]] -- //"Every 3 gauge sizes the resistance, mass per unit, and cross section will double or halve."//
 +
 +
 +----
 +===Downloads==
 {{filelist>:reference:awg*&style=table&tableheader=1&tableshowdate=1&tableshowsize=1}} {{filelist>:reference:awg*&style=table&tableheader=1&tableshowdate=1&tableshowsize=1}}
 +
 +<wrap hide>[[http://wiresizecalculator.net/tables/groundconductortable.htm|ground conductor]]</wrap>
reference/awg-iec-wire.1433418158.txt.gz · Last modified: 2018/05/28 22:28 (external edit)