MetaTek Wire Color Standard

National Electrical Code (USA)

  • Grounded conductor (“neutral”): wires must be white or gray
  • Grounding conductor (“ground”): wires must be bare, green, or green/yellow striped
  • Orange, when used in a 3-phase 4 wire delta configuration supplying 120/240, shall designate the “wild” leg with 208v to neutral.

IEC Standards

The color of the grounded/neutral conductor is statutorily blue. PEN (Protective/Earth Neutral, combined) conductor, when insulated, shall be marked by one of the following methods:

  • Green-and-yellow throughout its length with, in addition, light blue markings at the terminations, or
  • Light blue throughout its length with, in addition, green-and-yellow markings at the terminations

120/240V Single-Phase

  • black, red and white

120/208V, Three-phase

  • black, red, blue and white

120/240V, Three-phase

  • black, orange, blue and white

277/480V, three-phase

  • brown, violet, yellow and gray

230V Single Phase

  • brown and white
  • brown and blue1)

230/400V Three Phase

  • brown, purple, yellow, gray
  • brown, purple, yellow, blue
  • Orange is the only specified ungrounded conductor and marks the “wild leg” of a 120/240 center-tapped neutral delta configuration. For those unfamiliar: In wild leg configuration, the two end phases on the center-tapped winding provide 120 volts to neutral, but on the wild leg you will find nearly 208 volts to the neutral. If you see an orange wire in a panel, alarm bells of caution should go off in your head. You don’t want to wire a 120 VAC outlet across the wild 208 volt phase.