Generators

Generators are sized for 30kw continuous/baseload, or 38kw prime power. The Generator Control System will automatically start a second generator if the first generator reaches 80% of its capacity, synchronize and operate them in parallel. When the load drops below 70% of the single genset capacity it will automatically unload and cool down the second genset.

  • Engine — John Deere 4045D
    • Subtract 20% from the 60Hz rating for 50Hz